ISO-RIG Replacement
Background:
ISO-NE
is responsible for managing electricity demand and ensuring a stable
supply in
New England
. Every generation facility that puts power on the grid must
have a remote intelligence gateway (RIG) system for receiving and
sending data to ISO-NE. ISO-NE has mandated that by February
2010 all existing RIGs must be updated. They left it up to
each plant to devise their own solution. The specifications are that the RIG communicates to ISO-NE using the
DNP3.0 subset level 2 over TCP/IP protocol and use the existing 56K
frame relay circuits. This specification greatly cuts down on the number of RTU
or software solutions available for this application.
Fitch
Solution:
Our solution
uses WonderWare InTouch for the front end and Triangle Microworks’
Scada Data Gateway software to communicate to ISO-NE. All the
necessary scripting is done in the InTouch system, so only a PC is
necessary. Other OPC servers can be used to obtain the data ISO-NE
requires such as MW, MVar, Voltage, Breaker Status, and AVR status
from the existing PLC or DCS systems.
HMI
applications that have an OPC client are able to connect to the
Scada Data Gateway software. Therefore if a customer has a
different HMI standard, a new project for this application can be
created with minimal effort. The Fitch Company solution
utilized is very open and easy to change. This is contrary to
other black box solutions. ISO-NE is pleased with the solution
in place. Feel free to contact them directly for a reference.
Contact us for more information.
More Specialty Applications